Optimization of Parameter Set for Statcom Control System
Loading...

Date
2010
Authors
Journal Title
Journal ISSN
Volume Title
Publisher
Ieee
Open Access Color
OpenAIRE Downloads
OpenAIRE Views
Abstract
STATCOM controlled power system shows highly non-linear characteristics. In such a structure, linear controllers are easy to apply but difficult to tune. Fine tuning of controller parameters is necessary to meet transient performance requirements. In this paper, control system parameters of a STATCOM which is constructed from two six-pulse voltage source based converters are optimized by Simplex algorithm which is a non-linear and non-gradient method. System objective function to be minimized is based on a performance index and expressed in terms of measured and desired values of system variables. After optimization, performance of STATCOM control system consisting of two PI controllers and two leag/lag compensators has been tested and verified through a number of simulation studies investigating step-response performance. Precise and quick responses have been observed with optimized parameters.
Description
ORCID
Keywords
Static synchronous compensator, STATCOM, PI controller, lead/lag compensator, multi-parameter optimization, Simplex algorithm